Call us today
+44 (0) 2380 632 059
  •  Front view of 2 items called 15W_25W_maintain connected to each other in a white background,
 

15W/25W Maintained Emergency Module

These modules are primarily used to provide emergency lighting for self-ballast lamps with a maximum load of 15W or 25W.

Installed as a maintained unit, these emergency modules will power a lamp of 25W and under at full brightness for duration of at least 3 hours should the main power fail. May also be used as a non-maintained unit.

The Emergency modules consist of a battery pack, an integrated emergency power module, charge indicator LED and a test switch. Built into the system is a discharge protection circuit for use with 12V Ni-Cd (high temp) battery pack.

Technical Specification

  • Duration: 3 hours
  • Recharge period: 72 hours
  • Mains input: 100 – 240 Volts
  • Battery input: 12VDC
  • Mains current: 0.7A
  • Charge current: 250mA
  • Charging method: Trickle charge
  • Discharge current: 1.6A
  • THD (Total Harmonic Distortion): < 15%
  • Charge indicator: Green LED
  • Changeover voltage: 17.5V
  • Emergency switch time: < 1 second
Product code Description
EMG91512-H 6W to 15W maintained emergency inverter & battery
EMG92512-H 6W to 25W maintained emergency inverter & battery